Suzhou Pullwin Auto Technology Co.,Ltd
Building 3, Meijite Industrial Product Expo Center No.1055, East Jinyang Road, Lujia Town Kunshan City
Wendy
0086-159-5093-1259
pullwin@pullwinsz.com
This device measures the current humidity value through polymer membrance installed in the filter. Relative humidity and dew point value are accurately showed on the monitor. Customers can set a dew point value to trigger the alarm through the buttons on the display. This device is anti-corrosion, suitable for extremely corrosive working conditions such as HCL Cl2
Features
☆ Using high-precision RH&T sensor
☆ Can observe current dew point value
☆ Can set alarm value freely according to different situation
☆ Din rail mounting moniter for easy and quick installation
☆ Polymer Membrance installation can protect the sensor from being damaged by corrosive gas, such as Cl2
Model | PW-DP48-M series |
Relative humidity range | 0~100%RH |
Relative humidity error | ±1.5%RH |
Temperature range | -40~60℃ |
Temperature range error | ±0.1℃ |
Dew point range | -40~60℃ |
Sensor installation | Polymer membrance |
Alarm output | 250V AC 1A NO ( normally open ) |
Monitor size | 50*70*100mm |
Monitor installation | Din rail |
Wire length | 1m or 1.5m or 2m ( optional ) |